Controllers Used For Water Chilling Applications, Liquid Chilling Applications, Manufacturer, Exporter, Supplier, Proton Power Control, Pune, Maharashtra, India

Single Phase Chiller Controllers

1.Under normal working condition at power on after delay of 1 min.FAN1 will Start (ON),after 2 mins.FAN2 Starts(ON),after 3 min delay Compressor will Starts(ON). 2.While compressor is ON,if HP,LP,OL occurs then Compressor and FAN2 will be Shut Down(OFF). 3.IF UV /OV occurs then Both FANs and compressor will be Shut Down(OFF).

  • Supply Voltage: 230 VAC ± 15 %.
  • Output Contact Rating:
  • 30A,250V for Compressor.
  • 7Amps,at 250 VAC for FAN1/FAN2.
  • Front Panel:
  • 1) 3 seven Segment bright LED Display.
  • 2) 3 Keys for settings.
  • 3) Fault indication by Red LED.
  • 4) Compressor,FAN1/2 Green LED.
  • Sensing:
  • 1) Temperature, HP, LP for compressor.
  • 2) Current & Voltage sensing.

 

  • Run Mode Parameters:
  • 1) Voltage.
  • 2) Current.
  • 3) Fault(If any) indication(UL,OL,UV,OV)
  • 4) Status of Pump(On/Off).
  • Faults/Protections:
  • 1) Under Load(DryRun).
  • 2) Over Load.
  • 3) Under Voltage

  • N/A